JUNXY Series Resistive & Inductive AC Load Banks

JUNXY Series Resistive & Inductive AC Load Banks

JUNXY resistive & inductive AC load banks are used to simulate the motor loads or other electromagnetic devices working at their rated power factor. Many backup generators and turbines are rated at 0.7, 0.8 or 0.85 power factor and need to be commissioned at nameplate capacity using a combination of resistive and reactive load to fully qualify their operating capability. Using a resistive & reactive load bank enables comprehensive testing from a single unit.

JUNXY has an extensive range of resistive & reactive load banks to simulate these types of loads on a power source and the transformers, relays, and switches which will distribute the power throughout your facility. 

JUNXY resistive & inductive load banks-RL

Models

AC230V-6kW-RL

AC480V-30kW-RL

AC480V-60kW-RL

AC480V-100kW-RL

AC480V-200kW-RL

AC480V-500kW-RL

Capacity

Resistive load:
6kW
Inductive load:
4.5kVAR

Resistive load:
30kW
Inductive load:
22.5kVAR

Resistive load:
60kW
Inductive load:
45kVAR

Resistive load:
100kW
Inductive load:
75kVAR

Resistive load:
200kW
Inductive load:
150kVAR

Resistive load:
500kW
Inductive load:
375kVA

Customized solutions could be available upon request.

Rated Voltage

Single Phase,

AC230V

Three Phase AC480V,

or units can be specified by customer

Customized solutions could be available upon request.

Rated current
at 480VAC

Resistive amperes per phase: 26A
Reactive amperes per phase: 20A

Resistive amperes per phase: 36A
Reactive amperes per phase: 27A

Resistive amperes per phase: 72A
Reactive amperes per phase: 54A

Resistive amperes per phase: 120A
Reactive amperes per phase: 90A

Resistive amperes per phase: 240A
Reactive amperes per phase: 180A

Resistive amperes per phase: 601A
Reactive amperes per phase: 451A

PF

PF=0.8

Minimum Load Step

100W, 100VAR

100W, 100VAR

100W, 100VAR

1kW, 1kVAR

1kW, 1kVAR

1kW, 1kVAR

Customized solutions could be available upon request.

Display

Voltage, Current, Frequency, Power and PF displayed by digital meter

Protection

Overheating alarm, Short circuit protection, Overheating protection, Fan overloading protection, Emergency stop button.

All protections can be configured optionally

Control Mode

Manual control by MCBs or push buttons

Air Flow

Horizontal, Force-air cooling

Dimension

51*50*110(cm)

90*90*160(cm)

90*90*200(cm)

120*120*200(cm)

90*90*200(cm)  

120*120*200(cm)     

Options

Handle panel or PC remote control selectable