JUNXY-240V/415V-40A-R Resistive AC Load Bank

×

Why load bank testing is important?

JUNXY series AC/DC load banks are for many power supplies load bank testing, to ensure that the standby power supply system say UPS(uninterrupted power supply), battery bank, generator, transformers, inverter etc which especially located in harsh, dusty or corrosive environment working in good condition, when you need them most, if switched to be loaded when the main power supply in maintenance procedure or stop abnormally.

The AC/DC load bank loading test preventative maintenance of such power supply systems could free you from power supply failure, to ensure constant uptime for your power systems and make you prepared for anything. Downtime could also be reduced by regular maintenance and thorough inspections which are the key to power supply systems maintenance.

Load bank testing could help highlight a large range of faults on the power supply systems it test. The first goal achieved when testing with JUNXY AC/DC load bank is to ensure your power supply system is reliable or not by validating the power systems’ outputs to its technical specifications. The underlying question that JUNXY series AC/DC load bank could answer you is--“how is my power supply systems constant uptime(technical performance) ?” The load bank also tests that the power supply system is not faulty, no faults in construction and components reliable, that the aging of the power supply system is in line with expectations and that there are no pending breakdowns or early signs of wear and tear.

JUNXY offers you whole AC/DC load bank testing solutions of predictive failure analysis for UPS(uninterrupted power supply), generator, transformers, PV system, inverter etc, to validate the condition and output of such power systems comprehensively. Integrated AC/DC load bank could be made in one unit or separately with different load voltages as per your need for different


JUNXY AC/DC load banks applications
  •   Battery bank system
  •   Energy storage system
  •   Energy meter loop load test
  •   Datacenter rack heat simulating
  •  PV system Inverter anti-islanding test
  •  Voltage regulator, rectifier aging load test
  •   Genset, UPS load bank commission testing
  •   AC/DC power supply, power source commission acceptance test
JUNXY series load banks loading elements (load bank types)

Alloy resistors, inductors & capacitors loading elements are combined used in JUNXY series AC/DC load bank as per clients’ need in different applications:

  •   Pure resistive AC load bank
  •   Pure resistive DC load bank
  •   RCD non-linear AC load bank
  •   Resistive & inductive combined AC load bank
  •   Resistive, inductive & capacitive combined AC load bank

Wide volage range AC load bank with load input voltage 0-240V single phase adjustable, 0-415V line voltage adjutable, 0-40A adjustable for different load voltage.

Vary AC load bank with adjutable voltage & current. Regulator load bank test, Lab test, short circuit test

Technical Specifications
Model JUNXY-AC415V-40A-R Resistive AC Load Bank
Load
Element
Alloy
resistors
Load Voltage AC415V 3 phase 4 Wire, 50Hz, or lower voltage

(Load Voltage
DO NOT exceed AC415V)

Load Step(ohm) Phase A: 0.1, 0.2, 0.2, 0.5, 1, 1, 2, 2, 5, 10,
20, 40, 60, 100(Ω)

Phase B: 0.1, 0.2, 0.2, 0.5, 1, 1, 2, 2, 5, 10,
20, 40, 60, 100(Ω)

Phase C: 0.1, 0.2, 0.2, 0.5, 1, 1, 2, 2, 5, 10,
20, 40, 60, 100(Ω)

(0.1
to 242 ohm adjustable per phase)

Power Factor PF=1
Load Accuracy ±5%
Digital Meter Voltage, Current,
Power, Frequency and etc.
Power Supply 240V 50Hz, single phase
Control Mode Manual local panel control by push button
Insulation Class F
Protection Level IP20(indoor use)
Fan Noise 75dB
Cooling Mode Vertical force-air
cooling
Work Mode Continuous work
Protections Overheating/buzzer
alarm, overheating/over current protection, emergency stop button
Ambient Temperature -10℃~+50℃
Dimension 600*850*1260mm
Weight 180KG
Mobility Four wheels, lifting rings in chassis top
Humidity ≤95%
Altitude ≤2500 meters