| Technical Specifications | ||
|---|---|---|
| Model | JUNXY-AC415V-7KW-RLC AC Load Bank | |
| Load Element | Resistor, inductor & capacitor | |
| Dual Load Voltage | Dual Load Voltage | |
| Frequency | 50Hz | |
| 3 Phase Load Power | R=7KW(Active power @AC415V 3P4W & AC240V 1P2W) L=7KVar(Reactive power @AC415V 3P4W & AC240V 1P2W) C=7KVar(Reactive power @AC415V 3P4W & AC240V 1P2W) | |
| Load Steps @AC415V 3P4W | Resistive load steps: 100W-7KW adjustable 100W, 200W*2, 500W, 1KW, 2KW, 3KW Inductive load steps: 100Var-7KVar adjustable 100Var, 200Var*2, 500Var, 1KVar, 2KVar, 3KVar Capacitive load steps: 100Var-7KVar adjustable 100Var, 200Var*2, 500Var, 1KVar, 2KVar, 3KVar | |
| Load Steps @AC240V 1P2W | Resistive load steps: 100W-7KW adjustable 100W, 200W*2, 500W, 1KW, 2KW, 3KW (3phase in parallel connection) Inductive load steps: 100Var-7KVar adjustable 100Var, 200Var*2, 500Var, 1KVar, 2KVar, 3KVar (3phase in parallel connection) Capacitive load steps: 100Var-7KVar adjustable 100Var, 200Var*2, 500Var, 1KVar, 2KVar, 3KVar (3phase in parallel connection) | |
| Power Factor | Lead & lagging Power factor 0.7-1.0 adjustable | |
| Load Accuracy | Resistor/Capacitor: ±5%, Inductor: ±10% | |
| Digital Meter | voltage, current, active power, reactive power, apparent power, power factor, energy, frequency | |
| Mains Voltage | 220V 50Hz, single phase | |
| Control Modes | Local control panel by mini circuit breakers | |
| Load Input Wire Connections | Terminals for wire connections | |
| Insulation Class | F | |
| Protection Level | IP20(indoor use) | |
| Fan Noise | 75dB | |
| Cooling Mode | Force-air vertical cooling, by axial-flow fans. | |
| Work Mode | Continuous work | |
| Protections | Overheating/Buzzer alarm, Overheating/Over current, over voltage, over load protection, emergency stop button | |
| Dimension | 500*750*1100mm | |
| Weight | Around 170kg | |
| Ambient Temperature | -10℃~+50℃ | |
| Mobility | Four wheels | |
| Humidity | ≤95% | |
| Altitude | ≤2500 meters |