JUNXY-ACO380/20 (380V 200KW)

JUNXY-ACO380/20 (380V 200KW)

Regular maintenance and thorough inspections are the key to reducing downtime. Critical power backup equipment like a UPS System and generator will fail without proper preventative maintenance, especially when they are located in harsh, dusty or corrosive environments. Load Banks are devices designed to provide electrical loads for testing power sources such as generators and Unin- terruptible Power Supplies (UPS). Load banks are also used to reduce “wet stacking” problems in diesel engines of backup generating systems. JUNXY ENERGY builds custom preventative maintenance programs for UPS systems and generators to ensure you are prepared for anything.

 

Functions & Features

  • Set/adjust discharging power according to performance parameters and detection requirements

  • Set discharging time, timing to automatic shut-off load, discharge off and alarm operator

  • Set load voltage, over/under voltage and over current protection threshold value, it can shut off load, terminate discharging and alarm user automatically.

  • Set storage data sheet recording period optionally which must be more than the minimum period 6 Seconds.

  • Large screen LCD display, friendly interface, English menu, display discharge power, time, power consumption, every phase load voltage, current, frequency and inner temperature information real timely.

  • Parallel operation function to carry out multi sets load operation by RS 485 communication

  • Readjust discharge parameters during discharging process

  • Built-in storage function, save 10 groups of test data, which can be inquired, deleted and put into flash disk.

  • Start/stop discharging control by Serial port, and detect data real time operation etc; The storage data can be uploaded to PC by serial port or flash disk, and the upper computer’s software can analyze data and pattern and print report etc.

  • Terminal protection function, it can turn off load, terminate discharging and alarm automatically when over temperature.

  • Power Fail Recovery function.

  • Set at most 10 groups power, load process automatically according to the setting power and operation time after being turned on.

Technical Parameters:

Model

JX-ACO380/20 (380V 200KW)

Condition of Circumstance

Working Temperature: (-2055)℃        

Storage Temperature: (-4570)℃

Relative humidity: 90%(40±2℃)

Atmospheric pressure: (70106)KPa

External Dimensions(mm)

Approx 800*850*1350mm

Net Weight

250KG

Working Voltage

Single-phase 120V AC, 60Hz

Load voltage

Three-phase AC380V, Single-phase AC220V

Operating power

Stand-alone: Max 200KW (Three-phase 380V)

          Max 66KW (Single-phase 220V)

Parallel Operation: Sum of all stand-alones’ max power

Discharging Time

0~(19 hours and 59 minutes) Adjustable continuously

Temperature alarm & Threshold Value

75℃

Voltage measurement range

AC 0~450V, Display Resolution: 0.1V, Precision: ±5‰

Maximum Load Step

5 steps,

Minimum Load Step Resolution

1KW

Recording Period

6~999 Seconds

Current measurement range

AC 0~200A, Display Resolution: 0.1A, Precision: ±1

Frequency measurement range

45~65 Hz, Display Resolution: 0.1Hz, Precision: ±2‰

Power measurement range

0~200 KVA, Display resolution: 0.1KVA, Precision: ±1

Power factor measurement range

0.001-1.000 display resolution:0.001,Precision:±0.5

Cooling mode

FCT(Fan control Temperature)

Communication Mode

RS232

Data export

SD card

Display mode

8inch TFT

MTTF

≥50000h